Programming WM5 96
19
WM5-96 Instruction Manual
Let’s for example take into consideration the following tariff plan
decided by the energy supplier for December.
The working week is from Monday to Friday, while the weekend is
made by Saturday and Sunday. During the working days there are two
different tariffs with the following time periods: TARIFF 4 (T4) from 8
a
m to 5 pm, and TARIFF 3 from 5 pm to 8 am., while during the week
end there is only one time period and therefore a single TARIFF (T2).
The first thing to do is to program the week type (4 - 6), the working
days will be indicated as follows: Monday (W), Tuesday (W),
Wednesday (W), Thursday (W), Friday (W). While the weekend
(Holidays) will be indicated as: Saturday (H), Sunday (H). As a conse-
quence, the time periods relating to the working weeks will be divided
into the following lines (8 - 13):
First line: START TIME = 00, END TIME = 8, START DATE = 01/12,
END DATE = 31/12, then select “WORKING” and TARIFF “3”.
Second line: START TIME = 8, END TIME = 17, START DATE = 01/12,
END DATE = 31/12, then select “WORKING” and TARIFF “4”.
Third line: START TIME = 17, END TIME = 24, START DATE = 01/12, END
DATE = 31/12, then select “WORKING” and TARIFF“3”. Moreover, a 4th
line will be necessary to identify the NON-WORKING days other than the
week end (Saturday and Sunday): for example December 25th and 26th.
Fourth line: START TIME = 00, END TIME = 24, START DATE = 25/12,
END DATE = 26/12, then select “HOLIDAY” and TARIFF “2”.
The periods are now programmed and the instrument will display the
window on the left.
The periods programmed as above only refer to the month of
December, therefore it’s necessary to set a tariff referring to the
remaining time period, which will be referred to as “T1”. In this case
you can refer to the default tariff (14) set as TARIFF “1”, so that the
instrument will automatically r
efer to TARIFF “T1” when no other pro-
gramming is pr
esent.
P
rogramming example of the tariff
parameters
In the “time periods” table you have
at least 100 selection rows available.
ENERGY SUPPLIER SETTING WM5
Month Week Time Type
Selected
Tariff
Start time End time Start date End date Type Tariff
DECEMBER
fr
om
MONDA
Y
to
FRIDAY
from 8
to 17
Working
4 00 08 01/12 31/12 W 3
from 17
to 8
3
8 17 01/12 31/12 W 4
17 24 01/12 31/12 W 3
fr
om SA
TURDA
Y
toSUNDA
Y
H24 Holiday 2 00 24 25/12 26/12 H 2
Rest of the
year
All H24 -- 1 Default tarif
f 1
time day
W H T
00 08 01/12 31/12 03
08 17 01/12 31/12 04
17 24 01/12 31/12 03
00 24 25/12 26/12 02
line : 004
Page view 20