PowerSoft
PowerSoft Instruction manual 13
§ Recording interval [min]: it is the period of time after which the
variables set in the previous window are stored in the software
database. The recording occurs at the minutes that are integer multiple
of the recording time. For example if it is 10 minutes, the recordings
occur at minutes 00, 10, 20, 30, 40, 50. The minimum interval is 1
minute, so that it is possible to store 1440 records per day.
These recordings are in addition to the system recordings. If the system
integration time (see paragraph 1.3.1) is 15 minutes, the recordings
occur at minutes 00, 10, 15, 20, 30, 40, 45, 50.
§ Enable DI0: it enables the reading of the first digital input status,
if present on the instrument.
§ Enable DI1: it enables the reading of the second digital input
status, if present on the instrument.
Synchronize PC from Digital Input 1: it associates the clock
synchronisation function to the status change of digital input 1. The
clock is automatically set to the closest multiple of the “system
recording interval. If, for example, the system interval is 15 minutes,
and input 1 status changes at 10.39.12 the clock is automatically
updated to 1.30.00.
§ Synchronize PC from Digital Input 2: it associates the clock
synchronisation function to the status change of digital input 2. This
function can be set only in input 1, only in input 2 or in both of them.
§ Enable DO1: it enables PowerSoft to control the first digital
output (or output 0 of slot D in the 96x96 modular instruments). The