PROGRAMMING WM30-96
CARLO GAVAZZI
A
utomation Components
14
EXAMPLE OF ALARM PARAMETERS PROGRAMMING
It is required the disconnection of a load when a set value of absorbed
power occurs. For example when 300kW are exceeded, the alarm occurs
and the set load is disconnected.
An “UP” alarm is selected, below you’ll find the recommended program-
ming:
ENABLE: YES
VARIABLES: W system (W)
SET POINT 1: 300kW
SET POINT 2: 295kW
ON DELAY: set the desired number of seconds: “5 seconds”.
300kW
295kW